MO Minimum : Elevators
|
(E) - Machines
|
(E)4
|
|
|
Hoist rope tail retaining clips shall be properly spaced.
|
|
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
x
|
|
The emergency/standby power shall be tested.
|
11/7/2025
|
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
The car door shall be restricted from opening when in the closed position anywhere outside the unlocking zone. The car door restrictor is not currently working.
|
1/25/2024
|
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
The car lighting shall be externally guarded or coated to contain broken glass in case the bulb or tube accidentally breaks.
|
|
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
The car lighting shall be externally guarded or coated to contain broken glass in case the bulb or tube accidentally breaks.
|
11/7/2025
|
|
A17.1-1996 : Elevators
|
3.9 - Floor and emergency identification numbering
|
100.7
|
|
|
Car identification number shall be on the corsshead, at least 2" in height, and visible from the landing.
|
|
|
A17.1-1996 : Elevators
|
4.2 - Hoistway doors
|
110
|
|
|
Adjust uptrust roller bearings for proper clerance to door hanger track (10th floor, lower gap >0.75")
|
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site.
|
11/7/2025
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
11/7/2025
|