Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Phone in elevator cab still does not work, possible phone line problem. Re-inspection required 4/10/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Phone in elevator cab does not work. Re-inspection required 1/14/2025
MO Minimum : Elevators (I) - Pits (I)2 x x One of the car spring buffers was laying on its side in the elevator pit. All buffer stands and buffer springs are severly rusted out. Need to replace all buffer stands & buffer springs. Elevator Red-tagged and removed from service. Re-inspection required 1/14/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher is overdue for annual maintenance, need to have serviced or replaced.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher is expired in machine room, have serviced or replaced
MO Minimum : Elevators (H) - Machine Rooms (H)3 Fire extinguisher is overdue for annual maintenance, need to perform maintenance on fire extinguisher.
MO Minimum : Elevators (I) - Pits (I)5 Elevator pit ladder is loose due to bottom support being rusted off, repair or replace pit ladder
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be clean & dry. Pit has 10" of water in it
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light shall be made operable
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current operating certificate shall be displayed in the machine room