A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
MCP fire service testing must be properly documented monthly on log sheets.
|
7/18/2023
|
A17.1-1996 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
102.1
|
|
|
4x4 electrical box in the machine room needs to have wiring inside the box and cover installed.
|
7/18/2023
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test.
|
5/31/2023
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspection)
|
x
|
|
This elevator is equipped with an unsealed overspeed valve. A category 5 test shall be performed and witnessed on the overspeed valve in 2022.
|
5/31/2023
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
5/31/2023
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
x
|
The in car emergency telephone shall be operational with and without main power and give proper location. Elevator Red Tagged for multi-year phone violation.
|
6/2/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.7 Record of Oil Usage
|
|
|
MCP oil loss log testing to be properly documented on every visit on log sheet.
|
7/18/2023
|