Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. The log is not being filled out monthly.
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x The emergency/standby power shall be tested.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Pipe on the wall in machine room near #4 is leaking water on the floor. Take corrective action.
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x The car shall not hit the buffer before activating the final limit. Take corrective action. 10/7/2022
A17.1-1996 : Elevators 1.8 - Door closing force 1001.2(a)(8) x The door closing force shall not exceed 30 lbs. 10/7/2022