Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) The fire extinguisher in the elevator machine room is expired and shall be replaced or serviced. 7/13/2020
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 10/21/2021
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing The overspeed valve has an installation date of 2003. It shall be tested with the rated load on or before the next annual inspection. 8/16/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate There is no state operating certificate in the machine room. 10/19/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 8/30/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 5/25/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall remain operational when 110v source is removed. 7/24/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Provide existing phone to work with 24/7 support. 9/5/2018
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x In car emergency telephone shall work. 7/6/2020