MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Elevator cab phone does not work, phone line has not power. Re-inspection required
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Machine room illumination is less than 10 fc
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Machine room lighting is 1 to 2 foot candles at the machine room floor. Lighting shall be a minimum of 10 foot candles at the floor surface, need to provide adequate lighting
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Need to remove standing water from the pit and provide means to guide future water to sump pump for removal
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Auxiliary power lowering unit (emergency rescue unit) does not work. Power supply unit has been removed. Elevator controller has wiring for emergency rescue unit. Re-inspection required
|
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
|
|
Machine room illumination is less than 10 fc
|
9/26/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|