Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Elevator cab phone does not work, phone line has not power. Re-inspection required
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine room illumination is less than 10 fc
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine room lighting is 1 to 2 foot candles at the machine room floor. Lighting shall be a minimum of 10 foot candles at the floor surface, need to provide adequate lighting
MO Minimum : Elevators (I) - Pits (I)1 Need to remove standing water from the pit and provide means to guide future water to sump pump for removal
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Auxiliary power lowering unit (emergency rescue unit) does not work. Power supply unit has been removed. Elevator controller has wiring for emergency rescue unit. Re-inspection required
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting Machine room illumination is less than 10 fc 9/26/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room