Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)10 Means shall be provided on at least one upper landing to permit access the top of the car and at the bottom landing to access the pit.
MO Minimum : Elevators (A) - Hoistways (A)16 Replace all missing covers on electrical devices, including interlocks
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)6 Provide NO PASSENGERS signage and proper class loading signage in letters not less than 1/2" tall in conspicuous location in car
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)8 Car flooring is damaged. Repair or replace
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)4 Cartop shall be capable of supporting at least 200 lbs at any point
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)1 Provide an emergency exit with cover on cartop
MO Minimum : Elevators (F) - Electrical Switches (F)9 Main disconnect switch shall be fused, lockable & accessible in machine room. Current knife switch is not acceptable
MO Minimum : Elevators (F) - Electrical Switches (F)2 x Upper & lower limit switches shall not be open type. Re-inspection required
MO Minimum : Elevators (F) - Electrical Switches (F)6 x In car stop switch is wired closed. Switch shall be made operational. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A copy of the MCP shall be kept in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Provide a current fire extinguisher in machine room
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)4 Provide a crosshead data plate including year of install, manufacturer, rated load, car speed, number, size & type of hoist ropes.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.1.4(b)(2) Hydraulic elevators Placed out of Service x x Unit has not been inspected since 2013, requires Cat 5 testing. Final limit switch in pit failed. Red tagged elevator 6/10/2022