MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A copy of the MCP shall be kept in the machine room
|
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)9
|
|
|
Main disconnect switch shall be fused, lockable & accessible in machine room. Current knife switch is not acceptable
|
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)2
|
x
|
|
Upper & lower limit switches shall not be open type. Re-inspection required
|
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)6
|
x
|
|
In car stop switch is wired closed. Switch shall be made operational. Re-inspection required
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)10
|
|
|
Means shall be provided on at least one upper landing to permit access the top of the car and at the bottom landing to access the pit.
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
Replace all missing covers on electrical devices, including interlocks
|
|
MO Minimum : Elevators
|
(K) - Car Platforms and Car Slings
|
(K)4
|
|
|
Provide a crosshead data plate including year of install, manufacturer, rated load, car speed, number, size & type of hoist ropes.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Provide a current fire extinguisher in machine room
|
|
MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)6
|
|
|
Provide NO PASSENGERS signage and proper class loading signage in letters not less than 1/2" tall in conspicuous location in car
|
|
MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)8
|
|
|
Car flooring is damaged. Repair or replace
|
|
MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)4
|
|
|
Cartop shall be capable of supporting at least 200 lbs at any point
|
|
MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)1
|
|
|
Provide an emergency exit with cover on cartop
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11.1.4(b)(2) Hydraulic elevators Placed out of Service
|
x
|
x
|
Unit has not been inspected since 2013, requires Cat 5 testing. Final limit switch in pit failed. Red tagged elevator
|
6/10/2022
|