Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods This unit has had a drop ceiling installed and the bolts are sticking through the car top, the bolts need to be cut off so that they don't cause a tripping hazard for the maintenance personnel working on the cartop
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher is expired. Have serviced or replaced
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators (I) - Pits (I)1 Pit needs to be cleaned
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Cartop needs to be cleaned
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b Air conditioning unit in machine does not appear to be operating, needs repaired
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not working properly. Check & repair this phone for proper operation. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods x A new drop ceiling has been installed at some point with the anchor bolts protruding through the car top approximately 4". The anchor bolts shall be cut off smooth on the car top as not to cause a tripping hazard or potential injury to maintenance or emergency personnel. This is the second notice about the anchor bolts, needs to be completed within 30 days. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts A new drop ceiling has been installed at some point with the anchor bolts protruding through the car top approximately 4”. The anchor bolts shall be cut off smooth on the cart top as not to cause a tripping hazard or potential injury to maintenance and emergency personnel.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current operating certificate shall be displayed in the machine room
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate. 12/3/2018
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not working properly. Check and repair this phone for proper operation and passenger safety. Reinspection required. 1/11/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x The phone in the elevator cab is not working properly. Re-inspection required 9/27/2024