Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate. 12/3/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts A new drop ceiling has been installed at some point with the anchor bolts protruding through the car top approximately 4”. The anchor bolts shall be cut off smooth on the cart top as not to cause a tripping hazard or potential injury to maintenance and emergency personnel.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current operating certificate shall be displayed in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods This unit has had a drop ceiling installed and the bolts are sticking through the car top, the bolts need to be cut off so that they don't cause a tripping hazard for the maintenance personnel working on the cartop
MO Minimum : Elevators (I) - Pits (I)1 Pit needs to be cleaned
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Cartop needs to be cleaned
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current copy of the state certificate shall be displayed in the machine room
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not working. Check & repair this phone for proper operation and passenger safety. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods x A new drop ceiling has been installed at some point with the anchor bolts protruding through the car top approximately 4". The anchor bolts shall be cut off smooth on the car top as not to cause a tripping hazard or potential injury to maintenance or emergency personnel. This is the second notice about the anchor bolts, needs to be completed within 30 days. Re-inspection required
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x The phone in the elevator cab is not working. Re-inspection required 9/27/2024
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV is not sealed and must have a cat 5 weight test performed within 90 days or less 3/30/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not working properly. Check and repair this phone for proper operation and passenger safety. Reinspection required. 1/11/2024