Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting The car ceiling lighting cover is missing and requires repair or replacement. 11/19/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 5/26/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work. 10/15/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Hoistway fascia missing between floors 3 & 4 shall be replaced.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace damaged lower guide shoe insert.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 6/14/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Hoistway fascia missing between floors 3 & 4 shall be replaced. 6/14/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods A code data tag shall be installed. 6/22/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 6/22/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A machine room fire extinguisher is expired and shall be serviced or replaced. 11/19/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers The fire extinguisher in the elevator machine room is expired. A current tested ABC type fire extinguisher shall be provided in the elevator machine room. 6/22/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The in car emergency telephone shall be operational. 6/19/2020
MO Minimum : Elevators (I) - Pits (I)1 Remove the water from the pit. The pit shall be kept dry. 11/19/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an overspeed valve that is due for category 5 testing on or before the next annual inspection. 6/14/2023
conversion conversion conversion - reinspect x In cab emergency telephone shall work. 5/30/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be displayed in the elevator machine room. 6/22/2021