MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not operate
|
4/14/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Remove scavenger pump from pit. Cylinder drain line needs to drain into pit collection container of no more than 5 gallons
|
5/10/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not operate
|
5/31/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Remove scavenger pump from pit
|
5/10/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
Emergency phone and emergency light do not operate.
|
4/15/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emegency phone dials out. Can not hear anyone on the other end. Bad phone or speaker volume on phone needs to be increased
|
12/15/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
pit has oil on floor needs to be cleaned
|
12/12/2024
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(d)
|
x
|
|
Post metal permanent record of acceptance test on controller
|
12/21/2023
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
Machine room fire alarm initiating device does not recall elevator. Retest machine room fire alarm initiating device.
|
12/22/2023
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
Test emergency fire recall alarm initiating devices
|
12/21/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state operating certificate inside the machine room
|
5/9/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
No current state operating certificate displayed, or on site.
|
5/9/2023
|