Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.1.4 Maintenance Records Unable to verify if wiring diagrams provided at location are job specific diagrams. Provide unit specific wiring diagrams. 12/5/2023
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.6 Steps x Multiple step tread cleats are damaged, forming a "sharp knife edge". Damaged step treads shall be replaced to conform to code. 9/23/2024
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5.2(i) Demarcation lighting x All demarcation lighting shall work. 9/23/2024
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning Escalator machine space shall be kept clean and free from excessive debris (dust, dirt, oil, etc.). Clean lower pit.
Missouri Minimum : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) display of certificate Current state operating permit shall be displayed.
Missouri Minimum : Escalators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing incomplete: Comb impact & step index testing still needs to be performed and witnessed.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.6 Steps x 8.6.8.6.5 - Multiple step tread cleats are damaged, forming a sharp "knife-edged". Damaged steps treads should be replaced to conform to code. (2nd Notice)
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5.2(i) Demarcation lighting x All demarcation lighting shall work. (2nd Notice)
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning Escalator machine spaces/pits shall be kept clean and free from excessive debris, dirt, dust, oil, etc. Clean upper and lower pits. (2nd Notice)
Missouri Minimum : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) display of certificate A current MO State operating certificate shall be obtained and displayed.
MO Minimum : Elevators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.14 Clean down 1/15/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Reversal switch shall work properly.