Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(A) x Repair and install main drive motor fan impeller. 8.6.1.6.1 Unit red tagged until repaired. 5/3/2021
Missouri Minimum : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) display of certificate Current state operating permit shall be displayed.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5.2(i) Demarcation lighting x All demarcation lighting shall work.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning Escalator machine space shall be kept clean and free from excessive debris (dust, dirt, oil, etc.). Clean lower pit.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.6 Steps x Multiple step tread cleats are damaged, forming a "sharp knife edge". Damaged step treads shall be replaced to conform to code.
conversion conversion conversion - reinspect x Demarcation lights inoperative 6/19/2018
conversion conversion n/a Demarcation lights inoperative, repair 2/19/2020