Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.6 Steps x Multiple step tread cleats are damaged, forming a "sharp knife edge". Damaged step treads shall be replaced to conform to code.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5.2(i) Demarcation lighting x All demarcation lighting shall work.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning Escalator machine space shall be kept clean and free from excessive debris (dust, dirt, oil, etc.). Clean lower pit.
Missouri Minimum : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) display of certificate Current state operating permit shall be displayed.
conversion conversion conversion - reinspect x Repair lift skirt seam approximately 6 steps below top landing and re-test step indexing 6/19/2018
conversion conversion conversion - reinspect x Repair left skirt seam 6 steps below top landing and re-test step indexing 5/21/2019
conversion conversion n/a Upper demarcation lights inoperative 1/21/2020
conversion conversion n/a Upper demarcation lights inoperative repair 1/21/2020
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.3 Step/Skirt Performance Index x The step index was exceeding the .4 maximum. The index was over .900 on the up unit 12/1/2023