Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x A category 5 test shall be performed. 3/5/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x A category 5 test shall be performed. 9/20/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 All the on site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x Fire service operation shall be tested. 3/5/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service operation shall be tested. 9/20/2022
A17.1-1996 : Elevators 2.9 - Guarding of exposed auxiliary equipment 104.1 Kick angles shall be installed around the machine room cable slots to keep items from falling into the hoistway.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State operating certificate in machine room 7/8/2020
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 The 120VAC car lighting branch circuit shall not supply the recently installed in-car information displays.
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x The emergency/standby power operation of the elevator shall be tested. 3/5/2022