Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) No storage allowed in Elevator equipment room that is not elevator related. 12/1/2022
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 Need in case of fire signs by each hall call button 12/1/2022
A17.1-2016 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Room and Machinery Space Nothing other than elevator related equipment is authorized to be stored in Elevator Equipment room 12/1/2022
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 Overspeed valve is not sealed. Will have to do a full load test on next annual inspection for test and seal valve. 12/16/2022
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x Five year OSV test to be performed on next inspection cycle 12/16/2022