Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No could not perform annual inspection because of water in pit and machine room lights not working 11/24/2020
MO Minimum : Elevators (I) - Pits (I)1 No No the pit was full of water, maintain dry pit 10/3/2025
MO Minimum : Elevators (I) - Pits (I)1 No No Water in the pit, provide means to prevent the accumulation of ground water in the pit 10/3/2025
MO Minimum : Elevators (I) - Pits (I)1 Yes No Water in the pit, provide means to prevent the accumulation of ground water in the pit - repeat violation, now requires reinspection 1/17/2026
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Replace missing ceiling tiles in the machine room 1/17/2026
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Do not store non-Elevator related items in the machine room 10/3/2025
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No machine room lights were not working 10/3/2025
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure Yes No replace the emergency light battery, it is dead 7/31/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) No No the maintenance control program is missing the instructions for code checkout procedures 10/3/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.10 replacement of Hydraulic jack,Plunger,Cylinder,Tanks,and Anticreep Leveling Device Yes Yes elevator fail the set test, could not figure out where the oil was going. unit was red tagged 11/18/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Foam pad on tank lid is decomposing and dropping into the tank, clean or replace the oil 10/3/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Missing pickup roller on the bottom landing hoistway door 10/3/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Replace burnt out cab ceiling lights, illumination inside the car does not meet the minimum requirements 10/3/2025