Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Elevator phone does not work, no voltage on phone line. Re-inspection required 5/22/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone shall be made operational, this was written up last year. Re-inspection required 1/20/2025
A17.1-1996 : Elevators 2.33 - Tanks 1206.5b Oil return lines currently run directly back to tank, preventing monitoring of oil leakage. Provide proper containers in pit to monitor oil loss. 8/16/2021
A17.1-1996 : Elevators 2.40 - Maintenance Records 210.1d Inspection Operation. Equipment covered within the scope of this Code shall be maintained in accordance with 8.6. 1/3/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2 way communication not working 5/22/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x If the emergency communication means is normally connected to the building’s main power supply, it shall automatically transfer to an alternate source(s) of power when normal power supply fails. 5/22/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV is not sealed. Perform OSV test, seal and tag upon completion. 5/4/2022
conversion conversion n/a 1) Horizontally sliding doors of automatic elevators must be provided with door closers arranged to close an open door automatically if the car leaves the landing zone for any reason. The 1st Floor hoistway door (2nd landing) does not close automatically from the fully open position. 6/19/2018
conversion conversion n/a 2) Hoistways and pits shall be kept free of dirt and rubbish and shall not be used for storage purposes. 6/19/2018