Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self closing & locking. Door does not close on its own, repair same 4/22/2022
MO Minimum : Elevators (I) - Pits (I)1 Pits shall be kept clean & dry. Clean pit of oil & oily pads 4/22/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Oil return line in pit shall not be run directly into hydraulic tank in machine room. Reposition line & provide proper container to collect oil leakage. Patch/fire caulk hole in hoistway & MR walls from removal of line 4/22/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone & alarm shall both work 4/22/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency lighting shall work 4/22/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current state operating certificate shall be properly displayed in machine room 4/22/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current fire extinguisher shall be hung in machine room 4/22/2022
MO Minimum : Elevators (I) - Pits (I)8 Sump hole cover is plywood, replace w/noncombustible material fastened to pit floor, such as metal plate or grating capable of supporting workmen 4/22/2022
MO Minimum : Elevators (A) - Hoistways (A)13 Wall in pit around duct needs to be patched or fire caulked 4/22/2022
MO Minimum : Elevators (S) - Fire Service (S)1 x x Existing heat & smoke detectors shall be tested to verify proper operation with elevator controls 4/22/2022
MO Minimum : Elevators (A) - Hoistways (A)1 Both landings shall have finished flooring installed at sill to prevent tripping hazard 4/22/2022