Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
Missouri Minimum : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) display of certificate No No POST CURRENT STATE CERTIFICATE. 3/5/2026
Missouri Minimum : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) display of certificate No No Post current state certificate in machine room 11/3/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Provide current State certificate--Not done 3/2/2021
Missouri Minimum : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) display of certificate No No Post current State certificate in machine room 3/2/2021
Missouri Minimum : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) display of certificate No No Post current MO State operating certificate in machine space
conversion conversion n/a No No Unit needs to be cleaned down 8/28/2018
conversion conversion n/a No No Unit needs to be cleaned down 8/28/2018
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.7 Rollers, Tracks, and Chains Yes No REPLACE WORN HANDRAIL DRIVE CHAIN. POST CURRENT STATE CERTIFICATE 3/5/2026
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5.2(i) Demarcation lighting Yes No Replace worn demarcation strips on the side of step treads 11/3/2025
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(F) No No Adjust Upper section deck - for smooth joints 11/3/2025
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.6 Steps Yes Yes Brake Torque did not meet minimum when tested repair/replace brake REd TAGED 9/13/2022
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.6 Steps Yes No Gear box leaking oil visible on step treads... repair 9/13/2022
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.1.4 Maintenance Records No No Provide a maintenance control program on site posted on controller 3/2/2021
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(F) No No Secure raised section of deck 3/2/2021
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(C) No No Gear box seals leaking, evidence of oil on steps, correct problem 3/2/2021
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2 No No Unit needs clean down 3/2/2021
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.2 Escalator Step-to-Skirt Clearance Yes No Make repairs step indexing failed 11/10/2020
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(G) No Yes Both sides failed step skirt indexing 7/2/2019
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(F) No Yes Brake test failed due to oil leak on brake 7/2/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Secure raised section of deck---Not done 3/2/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Provide maintenance control plan--Not done 3/2/2021