Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2 Unit needs clean down 3/2/2021
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(C) Gear box seals leaking, evidence of oil on steps, correct problem 3/2/2021
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(F) x Brake test failed due to oil leak on brake 7/2/2019
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(F) Secure raised section of deck 3/2/2021
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(F) Adjust Upper section deck - for smooth joints
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(G) x Both sides failed step skirt indexing 7/2/2019
Missouri Minimum : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) display of certificate Post current State certificate in machine room 3/2/2021
Missouri Minimum : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) display of certificate Post current state certificate in machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Provide current State certificate--Not done 3/2/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide maintenance control plan--Not done 3/2/2021
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.1.4 Maintenance Records Provide a maintenance control program on site posted on controller 3/2/2021
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5.2(i) Demarcation lighting x Replace worn demarcation strips on the side of step treads
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Secure raised section of deck---Not done 3/2/2021
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.2 Escalator Step-to-Skirt Clearance x Make repairs step indexing failed 11/10/2020
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.6 Steps x x Brake Torque did not meet minimum when tested repair/replace brake REd TAGED 9/13/2022
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.6 Steps x Gear box leaking oil visible on step treads... repair 9/13/2022
conversion conversion n/a Unit needs to be cleaned down 8/28/2018
conversion conversion n/a Unit needs to be cleaned down 8/28/2018