Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light damaged, repair or replace as needed.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
MO Minimum : Elevators (I) - Pits (I)1 Standing water in the pit. Provide means to remove.
MO Minimum : Elevators (I) - Pits (I)1 Supply sump pump to maintain a dry pit
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing incomplete. Provide relief/stop ring test, record pressure.Provide 15 minute stand test.