Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide on site maintenance logs. 5/18/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate. 5/18/2020
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 Unsealed. Provide testing 1/8/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Oil minder in machine room not working. Repair as needed. 1/8/2022
A17.1-1996 : Elevators 2.36 - Hydraulic Cylinders 302.3 Hydraulic jack needs repacking. Leaking in pit. 5/18/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a x Clean oil out of pit. 4/1/2020
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV in the pit is unsealed, provide testing. 7/12/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone is not working correctly, repair as needed. 7/12/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone in elevator does not work. Code 2.27.1.1.1 11/12/2024