MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Light bulbs in car are not guarded to prevent injury to passengers in event of bulb breakage. Install tubes and end caps over all bulbs or install solid panels in drop ceiling, not open egg crate type as in present.
|
11/16/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Light bulbs in car are not guarded to prevent injury to passengers in event of bulb breakage. Need to install tubes & end caps over all bulbs or install solid panels in drop ceiling, not open egg crate type
|
11/16/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Light bulbs in the car are not guarded to prevent injury to passengers in event of bulb breakage. Install tubes and end caps over all bulbs or install solid panels in drop ceiling not open egg crate type as in at present.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher in machine room is expired, replace or have serviced.
|
11/16/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Machine room has been under water, need to clean machine including removing water from pump unit pan
|
11/16/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit has standing water, sump pump has been removed, need to replace sump pump
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit has standing water, sump pump has been removed, need to replace sump pump
|
11/16/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean pit of water and oil.
|
11/17/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
A 17.1 5.1.1.1(e) PIT ACCESS, LIGHTING, STOP SWITCH, AND CONDITION - STANDING WATER IN PIT
|
11/17/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit has been under water, need to clean pit
|
11/16/2023
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)2
|
|
|
Car dropped 2 1/2" during 15 min. static test. Oil leaking back through control valve. Repair/replace valve. 2.32
|
11/17/2020
|
conversion
|
conversion
|
n/a
|
|
|
Car dropped 2 1/2 during 15 minutes standing test control valve is leaking back into tank
|
11/17/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be on display in the machine room
|
11/16/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the elevator machine room
|
|