Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 Pit has standing water, sump pump has been removed, need to replace sump pump
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the elevator machine room
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Light bulbs in the car are not guarded to prevent injury to passengers in event of bulb breakage. Install tubes and end caps over all bulbs or install solid panels in drop ceiling not open egg crate type as in at present.
conversion conversion n/a Car dropped 2 1/2 during 15 minutes standing test control valve is leaking back into tank 11/17/2020
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)2 Car dropped 2 1/2" during 15 min. static test. Oil leaking back through control valve. Repair/replace valve. 2.32 11/17/2020
MO Minimum : Elevators (I) - Pits (I)1 Clean pit of water and oil. 11/17/2020
MO Minimum : Elevators (I) - Pits (I)1 A 17.1 5.1.1.1(e) PIT ACCESS, LIGHTING, STOP SWITCH, AND CONDITION - STANDING WATER IN PIT 11/17/2020
MO Minimum : Elevators (I) - Pits (I)1 Pit has been under water, need to clean pit 11/16/2023
MO Minimum : Elevators (H) - Machine Rooms (H)4 Machine room has been under water, need to clean machine including removing water from pump unit pan 11/16/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Light bulbs in car are not guarded to prevent injury to passengers in event of bulb breakage. Install tubes and end caps over all bulbs or install solid panels in drop ceiling, not open egg crate type as in present. 11/16/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher in machine room is expired, replace or have serviced. 11/16/2023
MO Minimum : Elevators (I) - Pits (I)1 Pit has standing water, sump pump has been removed, need to replace sump pump 11/16/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be on display in the machine room 11/16/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Light bulbs in car are not guarded to prevent injury to passengers in event of bulb breakage. Need to install tubes & end caps over all bulbs or install solid panels in drop ceiling, not open egg crate type 11/16/2023