ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.5 - Normal terminal stopping device
|
8.11.2.1.3(g)
|
x
|
|
Car shall have functioning Normal Terminal Limits actuating before Final Terminal Limit.
|
6/28/2022
|
conversion
|
conversion
|
n/a
|
|
|
Hoistway doors shall have fire stops
|
10/8/2019
|
conversion
|
conversion
|
n/a
|
|
|
Car door force shall be less than 30
|
10/8/2019
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current Operating Certificate in Machine Room
|
8/1/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.4 Plunger Gripper Testing
|
|
|
Plunger Gripper due to be tested with rated load recurring every 5 years.
|
8/1/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.1 Making Safety Devices Inoperative or Ineffective (Re-Inspection)
|
|
|
Relocate Plunger Gripper encoder so that it is not struck by the car during the stop ring pressure test
|
8/1/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.1 Making Safety Devices Inoperative or Ineffective (Re-Inspection)
|
|
|
Final limit Cam strikes overhead during stop ring pressure test
|
8/1/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone fails to establish two-way communication.
|
5/8/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone fails to establish two-way communication.
|
|