Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone fails to establish two-way communication. 5/8/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone fails to establish two-way communication.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current Operating Certificate in Machine Room 8/1/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.5 - Normal terminal stopping device 8.11.2.1.3(g) x Car shall have functioning Normal Terminal Limits actuating before Final Terminal Limit. 6/28/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.1 Making Safety Devices Inoperative or Ineffective (Re-Inspection) Relocate Plunger Gripper encoder so that it is not struck by the car during the stop ring pressure test 8/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.1 Making Safety Devices Inoperative or Ineffective (Re-Inspection) Final limit Cam strikes overhead during stop ring pressure test 8/1/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.4 Plunger Gripper Testing Plunger Gripper due to be tested with rated load recurring every 5 years. 8/1/2022
conversion conversion n/a Hoistway doors shall have fire stops 10/8/2019
conversion conversion n/a Car door force shall be less than 30 10/8/2019