Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)1 No No Car Door Restrictor does not work. Repair and Reinspect. 1.18
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency Phone in car fails to establish two-way communication 5/15/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Relocate tape selector mounting bracket on car top. Hits selector tape mounting bracket when doing stop ring pressure test
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Car shall have functioning Normal Terminal Limits actuating before Final Terminal Limit. 8/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Selector Reader head hits selector tape mounting bracket during stop ring pressure test 8/1/2022
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No There is water on the machine room floor. Machine rooms need to be kept clean and dry.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current Operating Certificate in machine room 8/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No The fire extinguisher in the machine room is due to be serviced or replaced
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace knocked out Down Hall Call Button at the second landing
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces No No Standing water on machine room floor and in front of controller creating electrical hazard 8/1/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.4 Plunger Gripper Testing No No Plunger Gripper due to be tested with rated load recurring every 5 years. 8/1/2022
conversion conversion n/a No No machine room shall be kept clean and dry
conversion conversion n/a No No No current state operation certificate in elevator machine room.