Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a No No Machine room light shall be guarded
conversion conversion n/a No No No current state operation certificate in elevator machine room.
conversion conversion n/a No No Car door closing force in excess of 30lbs
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) No No car door restrictor does not work. 10/17/2019
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No test phase 1 and 2 fire service. 10/17/2019
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)6 Yes Yes test life jacket type safety with full load. reinspection required. not a red tag. 10/17/2019
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Repair machine room lighting.
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Secure gutter under piping in machine room (head clearance issue).
MO Minimum : Elevators (A) - Hoistways (A)16 No No Large electric junction box in hoistway is missing its cover. Reinstall.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) Yes No Large head for floor leveling was torn off during stop ring test. No part of the car shall strike the overhead. 12/3/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Test elevator cab phone. 12/3/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Relocate car top selector tape bracket. Selector hits bracket when doing stop ring pressure test.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current operating certificate in machine room 8/1/2022
MO Minimum : Elevators (I) - Pits (I)1 No No All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. (Oil and rags in Pit) 8/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No Replace missing Up Thrust on top landing hall door 6/28/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Car shall have functioning Normal Terminal Limits actuating before Final Terminal Limit. 8/1/2022
MO Minimum : Elevators (I) - Pits (I)1 No No All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. (Oil and rags in Pit)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance No No Where pressure piping, valves, and cylinders use packing glands or seals, they shall be examined and maintained to prevent excessive loss of fluid.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency Phone in car fails to establish two-way communication 5/15/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No The fire extinguisher in the machine room is due to be serviced or replaced.