Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. (Oil and rags in Pit) 8/1/2022
MO Minimum : Elevators (I) - Pits (I)1 All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. (Oil and rags in Pit)
conversion conversion n/a Car door closing force in excess of 30lbs
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) car door restrictor does not work. 10/17/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Car shall have functioning Normal Terminal Limits actuating before Final Terminal Limit. 8/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency Phone in car fails to establish two-way communication
MO Minimum : Elevators (A) - Hoistways (A)16 Large electric junction box in hoistway is missing its cover. Reinstall.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Large head for floor leveling was torn off during stop ring test. No part of the car shall strike the overhead. 12/3/2019
conversion conversion n/a Machine room light shall be guarded
conversion conversion n/a No current state operation certificate in elevator machine room.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room 8/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Relocate car top selector tape bracket. Selector hits bracket when doing stop ring pressure test.
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Repair machine room lighting.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Replace missing Up Thrust on top landing hall door 6/28/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 Secure gutter under piping in machine room (head clearance issue).
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Test elevator cab phone. 12/3/2019
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)6 x x test life jacket type safety with full load. reinspection required. not a red tag. 10/17/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x test phase 1 and 2 fire service. 10/17/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance Where pressure piping, valves, and cylinders use packing glands or seals, they shall be examined and maintained to prevent excessive loss of fluid.