Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Repair phone in car 8/31/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Need maintenance control program on site and place on controller 8/6/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No No Need testing procedures included in MCP 6/23/2021
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service testing and document on log in machine room 6/1/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 1002.2g (Standby Power Operation) Yes No Repair emergency battery lowering unit 7/20/2023
A17.1-2016 : Elevators 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) 8.6.11.1 Firefighters’ Emergency Operation No No Perform Monthly Fire Service Test and Document on the Log Posted in the Machine Room. 11/21/2025
conversion conversion n/a No No Post current State certificate in machine room 8/6/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state certificate in machine room 6/23/2021
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post Current State Certificate in the Machine Room. 11/21/2025