Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Battery lowering function shall be operational. 4/27/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 4/27/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 4/23/2021
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 3/24/2022
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d The machine room door shall be self-closing and self-locking, and shall be operable from the interior space without the use of a key. 7/6/2023
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. 7/6/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 7/6/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 3/24/2022
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) All non-elevator related items shall be removed from the elevator machine room. 3/24/2022
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 Clean the pit of dirt and debris. 7/6/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 7/6/2023