Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 4.2 - Hoistway doors 110 Yes No 110.1 entrance that are rusted must be replaced 5/11/2026
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d No No Machine room door not self closing 2/14/2024
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d No No Machine room door not self closing and AC unit blocks access to controller 2/14/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a Yes No MUST CLEAN PIT 5/11/2026
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 No No MUST INSTALL SUMP PUMP COVER 5/11/2026
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 102 Yes No MUST REPLACE ALL WIRING AND CONDUIT THAT IS CORRODED/RUSTED AND FALLING APART 5/11/2026
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No PHONE MUST BE MADE OPERABLE 5/11/2026