A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
101.3d
|
|
|
Machine room door not self closing and AC blocks access to controller
|
10/5/2025
|
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
101.3d
|
|
|
Machine room door not self closing
|
10/5/2025
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
MUST INSTALL SUMP PUMP COVER
|
|
|
A17.1-1996 : Elevators
|
4.2 - Hoistway doors
|
110
|
|
|
110.1 entrance that are rusted must be replaced
|
|
|
A17.1-1996 : Elevators
|
5.9 - Buffers and emergency terminal speed limiting devices
|
201
|
x
|
|
Replace buffers and buffer stands due to corrosion/damage
|
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
102
|
x
|
|
MUST REPLACE ALL WIRING AND CONDUIT THAT IS CORRODED/RUSTED AND FALLING APART
|
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
THE PHONE MUST BE MADE OPERABLE
|
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a
|
x
|
|
MUST CLEAN ALL RUST
|
|