Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x THE PHONE MUST BE MADE OPERABLE
A17.1-1996 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 201 x Replace buffers and buffer stands due to corrosion/damage
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 102 x MUST REPLACE ALL WIRING AND CONDUIT THAT IS CORRODED/RUSTED AND FALLING APART
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 MUST INSTALL SUMP PUMP COVER
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a x MUST CLEAN ALL RUST
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d Machine room door not self closing and AC blocks access to controller 10/5/2025
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d Machine room door not self closing 10/5/2025
A17.1-1996 : Elevators 4.2 - Hoistway doors 110 110.1 entrance that are rusted must be replaced