Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Pit light shall work. 2/18/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room. 2/18/2021
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) Remove all non elevator related items from the elevator machine room. 9/20/2023
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Repair inoperative emergency light. 2/18/2021
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 3.8 The buffer piping in the elevator pit shall be replaced due to rusting.
A17.1-1996 : Elevators 2.13 - Governor,overspeed switch and seal 205.15 x Remote governor trip key switch in controller does not work. Cannot trip governor at contract speed with weights. Repair and reinspect within 30 days. Complete full load testing. 2/13/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test incomplete. The following tests need to be performed to complete test: counterweight buffer testing, up intended movement and generator testing. Re-inspection required