A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.5.14.3(f)
|
x
|
|
Emergency Recovery System not working issue needs repaired or replaced.
|
10/22/2024
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency telephone not working phone being replaced by contractor.
|
10/22/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.5.14.3(f)
|
x
|
|
emg lowering not working
|
10/25/2023
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
emg. phone not working
|
10/25/2023
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2(b)(5)
|
|
|
need write up for testing overspeed valve
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
no current cirt. displayed
|
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.13
|
|
|
OSV needs tested, sealed and tagged. Unit was sealed not tagged as to date tested. Weights not available must retest with Full Load.
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
phone not working
|
10/27/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State Operating Certificate not available.
|
|