Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Auxiliary lowering unit (emergency rescue unit) does not work. Re-inspection required 11/20/2023
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 OSV is not sealed and must have a cat 5 weight test performed within 90 days or less 10/28/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone in elevator cab does not work 10/28/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide on-site maintenance records. 11/4/2020