MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
Replace electrical junction box mounted mid tower. Corrosion has exposed wiring inside the box
|
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)9
|
|
|
Replace mainline disconnect. Disconnect can not be opened.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
no current operating cirt.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
missing backup roller on stile .
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
tower mast cross bracing rusted thru in places
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)2
|
|
|
rusty car top rusty angles holding up car top
|
|
MO Minimum : Elevators
|
(K) - Car Platforms and Car Slings
|
(K)1
|
|
|
underside of platform rusted
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)7
|
|
|
pit access sw not working
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
no MCP on site
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11.1.4(b)(1) Electric elevators Placed out of Service
|
x
|
x
|
elevator red tagged out of serv. for missing part an rust issuses on car an tower
|
2/15/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Replace hoistway gates that are corroded through the gate frame.
|
8/11/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Replace car gates that are corroded through gate frame
|
8/11/2021
|