Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 2/7/2024
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean and dry. Remove the oil from the pit floor. 2/7/2024
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The permanent lighting fixture in the pit shall have a switch that is accessible from the pit access door. 2/7/2024
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Lighting in the machine room shall be not less than (10) foot-candles at floor level. 2/7/2024
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The machine room needs more light. Lighting in the machine room shall be not less than 10 foot-candles at floor level. 2/7/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers The fire extinguisher is expired.An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. Note: Extinguisher is expired. 2/7/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Unit is running with the car and hoistway doors in the open position. Elevator locked out by maintenance company until violation is corrected.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. 2/7/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Need to determine if this unit has a single bottom jack. If the jack is single bottom type it is required to be replaced, or a governor with safeties installed, or a plunger gripper installed on the unit. Documentation shall be available on-site about the jack type. 2/7/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) 11/30/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements 8.6.5.8 - Single bottom jack. 2/7/2024