A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
Repair emergency light in car
|
12/13/2018
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
provide monthly fire service test & document on log in machine room
|
2/1/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
provide maintenance control program
|
2/1/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state certificate in machine room
|
2/1/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Perform monthly fire service test & document on log in machine room
|
2/1/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Celan oil from the pit floor
|
2/1/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
Provide maintenance control program
|
2/1/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean oil from pit floor
|
12/31/2022
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room.
|
|
A17.1-1996 : Elevators
|
1.16 - Rated load, platform area, and data plate
|
207
|
|
|
Capacity tag shall be installed in car.
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1002.2f
|
x
|
|
On fire service, doors will not close. Take corrective action and re-test.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
x
|
|
Repair/replace leaking overspeed valve & perform 5 year test;; Reinspection required
|
12/5/2023
|