Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Repair emergency light in car 12/13/2018
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log provide monthly fire service test & document on log in machine room 2/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records provide maintenance control program 2/1/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room 2/1/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service test & document on log in machine room 2/1/2022
MO Minimum : Elevators (I) - Pits (I)1 Celan oil from the pit floor 2/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation Provide maintenance control program 2/1/2022
MO Minimum : Elevators (I) - Pits (I)1 Clean oil from pit floor 12/31/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required shall be provided in the machine room.
A17.1-1996 : Elevators 1.16 - Rated load, platform area, and data plate 207 Capacity tag shall be installed in car.
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x On fire service, doors will not close. Take corrective action and re-test.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance x Repair/replace leaking overspeed valve & perform 5 year test;; Reinspection required 12/5/2023