Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect x No audible or visual signal on phase 1 fire service. 8/2/2018
conversion conversion n/a Replace expired battery in door restrictor control box. 9/23/2019
conversion conversion n/a In car emergency light shall work. 9/23/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting In cab emergency lights shall work. 9/23/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x In cab emergency alarm bell shall work. 10/3/2018
MO Minimum : Elevators (S) - Fire Service (S)1 x Door re-opening device (eye ray), sensitive to smoke, shall be overridden during Phase 1 and Phase 2 fire service operation. 10/3/2018
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Existing pit light shall work. 9/23/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 Existing car door restrictor shall work. - Reinspection Required 9/23/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The emergency lights and bell shall work. 9/23/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)10 Car Floors The carpet inside the elevator car is worn and frayed, creating a possible tripping hazard. Repair or replace as needed. 9/23/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current state operating certificate. 9/23/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 7/27/2021
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x There were no fire service keys to test fire service. Keys shall be kept on-site and fire service shall be tested. 11/28/2022
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal The Phase 1 fire service indicator light is not working. 7/2/2024