Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(5) Oil Leakage Collection Replace leaking jack gland seals, pit collection bucket overfills between maintenance visits
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a x Pit bucket was overflowing, clean up oil on pit floor
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.5.7 Record of Oil Usage Oil record log is not being filled out during maintenance visits, oil record log last filled out during 2024 annual inspection.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 the monthly fire service test log is not being filled out in the machine room 12/17/2020
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation monthly fire service test log is not being filled out monthly 12/1/2021
MO Minimum : Elevators (I) - Pits (I)1 Remove oil absorbent pads from the pit floor 2/27/2026