Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No the monthly fire service test log is not being filled out in the machine room 12/17/2020
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(5) Oil Leakage Collection No No Replace leaking jack gland seals, pit collection bucket overfills between maintenance visits
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a Yes No Pit bucket was overflowing, clean up oil on pit floor
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.5.7 Record of Oil Usage No No Oil record log is not being filled out during maintenance visits, oil record log last filled out during 2024 annual inspection.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation No No monthly fire service test log is not being filled out monthly 12/1/2021
MO Minimum : Elevators (I) - Pits (I)1 No No Remove oil absorbent pads from the pit floor 2/27/2026