A17.1-1996 : Elevators
|
1.7 - Car door or gate
|
204.4
|
|
|
CAR DOOR RESTRICTOR DOES NOT WORK
|
8/6/2024
|
A17.1-1996 : Elevators
|
1.8 - Door closing force
|
112.4(b)
|
x
|
|
FRONT DOOR CLOSING FORCE IS >30lbs
|
8/6/2024
|
A17.1-1996 : Elevators
|
3.9 - Floor and emergency identification numbering
|
100.7
|
|
|
Identify the inside of hoistway doors with numeral corresponding to landing floor.
|
10/20/2021
|
A17.1-1996 : Elevators
|
2.37 - Pressure Switch
|
306.14
|
x
|
|
Install low pressure switch on controller or disconnect
|
10/21/2021
|
A17.1-1996 : Elevators
|
2.14 - Code data plate
|
215
|
|
|
Post code data plate on controller or disconnect
|
10/20/2021
|