Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | x | x | Elevator will not return to normal operation from phase I and II Fireman Recall operation when reset with key. The only way to return elevator to normal operation is to disconnect power and then reconnect power. The bypass operation does not operate. A 30 day reinspection and repair is required. | 10/16/2019 |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Repair emergency phone. | 10/13/2021 |