MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Update maintenance and fire service records.
|
12/23/2019
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
Low oil pressure switch shall work.
|
12/23/2019
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Mechanical reversing edge is overridden on Fireman's emergency service Phase I recall. Edge should operate normally, repair same. Did not Red-tag, Re-inspection required
|
2/7/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Emergency battery lowering device is not working. Re-inspection required
|
2/7/2024
|