Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Car door reversing edge on front doors is not operating correctly, needs repaired. Re-inspection required
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x Overspeed valve is not sealed and must have a category 5 test performed on within 90 days or less 10/5/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone not working correctly. 3/8/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide a written maintenance control program on site including documents listed in section 8.6.1.2.2