MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation A written maintenance control program shall be kept on site 3/8/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit Clean pit. 3/8/2024
MO Minimum : Elevators (I) - Pits (I)1 Determine if sump pump works correctly, if not replace. 3/8/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Failed Phase I recall, has no Phase II 2/21/2024
MO Minimum : Elevators (I) - Pits (I)1 Need to determine if sump pump works correctly, if not it needs to be replaced
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate. 3/11/2024
MO Minimum : Elevators (I) - Pits (I)1 Remove oil from the sump hole. 3/8/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Reprogram emergency phone 7/18/2022
MO Minimum : Elevators (I) - Pits (I)1 Sump hole is filled with oil, needs to be removed